Name: Analog input module
Model: R60ADV8
Analog input channel number: 8CH.
accuracy
Ambient temperature of 25 plus or minus 5 degrees C: plus or minus 0.1%.
Ambient temperature 0 ~ 55 degrees C: plus or minus 0.3%.
Temperature coefficient.
Common
Conversion speed: 80 s/CH.
Channel to channel insulation.
Absolute maximum input: plus or minus 15V.
External wiring connection mode: 18 point screw terminal.
Voltage input
The analog input voltage: DC - 10 - 10V.
Digital output value: 32000 ~ 32000.
Current input
Analog input current: -.
Digital output value: -.
16 bit high resolution (1/32000).
No program can perform scaling and conversion operations.
The most suitable for the requirements of speed and accuracy of the detection equipment.
Easy to filter high frequency interference.
Execute event driven programs via alarm output.
Through the engineering software, the output of arbitrary analog waveform data.
Reduce downtime and reduce maintenance costs through anomaly detection
Works3 GX can be used to easily set the critical value of the input and output signals.
Can quickly detect the abnormal signal, so it can shorten the downtime, reduce maintenance costs.
Channel insulation can ensure the accurate signal transceiver.
Model with " -G " module in the channel between the insulation,
Isolation amplifiers are not required to prevent inter channel current and interference current.

Data transmission speed: 1G/100M/10M: bps.
Interface: RJ45 connector (MDI/MDI-X AUTO).
Maximum frame size: 1518/9022 (when using mega frame).
IP version: IPv4: correspondence.
At the same time, the number of open connections: 128.
Fixed cache: 5K word x 16.
Cache for random access: 6K word x 1.
Communication cable: 1000BASE-T standard Ethernet cable: 5E class above, (with double shield, STP) through cable MITSUBISHI R60ADV8 R60ADV8
Ethernet interface module with 2 Ethernet ports,
Can be used as Ethernet, IE CC-Link controller network (metal cable), IE Field CC-Link network with communication port. In addition,
The module has been adopted to facilitate the identification of the positive words and graphic dot matrix LED,
In order to quickly identify the communication status of the network MITSUBISHI R60ADV8.
Equipped with 2 Gigabit Ethernet ports support,
Communication of Ethernet, IE CC-Link controller network (metal cable) or IE Field CC-Link network.
The 2 Ethernet ports can be used in combination with other networks.
1 modules can support 2 kinds of network such as Ethernet and IE Field CC-Link network, which can reduce the cost of network construction MITSUBISHI R60ADV8.
In addition, the Ethernet communication can be simultaneously open 128 connections, which can be connected to more support for Ethernet devices.
Can support a variety of network module products.
Based on IE 1Gbps CC-Link, 128K word high-speed, large capacity network MITSUBISHI Input module.
1 modules support multiple networks.
Seamless communication through SLMP.
When an exception occurs, the communication can be continued through the ring back function MITSUBISHI Input module.
Support RS-422/485, RS-232 and other standard interface.
IQ-R MELSEC series contains a variety of network modules and interface modules,
From the computer layer (production management, information system) to the field layer (equipment system), to provide the most suitable for the purpose and use of the network MITSUBISHI Input module.
Open network IE CC-Link based on Ethernet is the core of the network.
IE CC-Link is an industrial open network with the flexible application of the world standard Ethernet technology,
Seamless connection can be realized from the controller layer to the field layer.
The use of SLMP, from the superior information system to the lower level of equipment, there is no need to consider the network layer.
Can be as 1 kinds of network generally seamless communication, whether in the office or inn the field,
Can easily achieve information collection, equipment monitoring and maintenance R60ADV8. In addition, using an Ethernet adapter module,
You can easily connect to the SLMP CC-Link universal Ethernet devices connected to the IEE Field network MITSUBISHI R60ADV8.
Therefore, no need to add a new network can effectively use the visual sensor, RFID controller, such as a variety of Ethernet devices.


...More relevant models >>>>
Last one: R60AD4
next one: R60ADI8